Effect of geometrical parameters on the evaporative heat transfer and pressure drop of R-134a flowing in dimpled tubes


Aroonrat K., Asirvatham L. G., DALKILIÇ A. S., Mahian O., Ahn H. S., Wongwises S.

HEAT AND MASS TRANSFER, cilt.57, sa.3, ss.465-479, 2021 (SCI-Expanded) identifier identifier

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 57 Sayı: 3
  • Basım Tarihi: 2021
  • Doi Numarası: 10.1007/s00231-020-02956-0
  • Dergi Adı: HEAT AND MASS TRANSFER
  • Derginin Tarandığı İndeksler: Science Citation Index Expanded (SCI-EXPANDED), Scopus, Academic Search Premier, Chimica, Compendex, INSPEC
  • Sayfa Sayıları: ss.465-479
  • Anahtar Kelimeler: Evaporation, Heat transfer, Pressure drop, Dimpled tube, HORIZONTAL SMOOTH, EMPIRICAL CORRELATIONS, NUMERICAL CORRELATION, GENERAL CORRELATION, CONDENSATION, PERFORMANCE, R-600A, R134A
  • Yıldız Teknik Üniversitesi Adresli: Evet

Özet

An investigation was experimentally performed to explore the influence of geometrical parameters on the evaporative heat transfer coefficient and pressure drop of R-134a in dimpled tubes. The test sections were the counter-flow tube-in-tube heat exchanger, where the refrigerant was evaporated in the inner tube and hot water flows in the annulus. Seven dimpled tubes with various helical pitches (p), dimpled pitches (z), and dimpled depths (e) were used as the test tubes. The test runs were carried out over mass fluxes of 300, 400, and 500 kg/m(2)s; heat fluxes of 20, 25, and 30 kW/m(2); and evaporating temperatures of 7, 10, and 13 degrees C. The results show the heat transfer enhancement factor (HF) and pressure drop penalty factor (PF) increase with a rise in e and a decrease in p and z. The HF and PF range between 1.03-1.7 and 1.76-9.00, respectively. The correlations for predicting the Nusselt number and the friction factor of R-134a during evaporation in dimpled tubes are proposed.