Disturbance Observer Based Control of Three Phase UPS Inverter


Unan S., Gorgun H., Bakan F.

18th Annual International Mediterranean Conference on Control and Automation (MED), Marrakech, Fas, 23 - 25 Haziran 2010, ss.321-326 identifier identifier

  • Yayın Türü: Bildiri / Tam Metin Bildiri
  • Doi Numarası: 10.1109/med.2010.5547688
  • Basıldığı Şehir: Marrakech
  • Basıldığı Ülke: Fas
  • Sayfa Sayıları: ss.321-326
  • Yıldız Teknik Üniversitesi Adresli: Hayır

Özet

In this paper control of three phase UPS inverter with cascaded PI controller and load current estimation via disturbance observer are presented. Pure sinusoidal waveform with specified amplitude and frequency is required for UPS inverter under variety of loads. Load current acts as disturbance on the plant. To increase the disturbance rejection of the plant, the load current is adopted as feed forward loop to the voltage controller. Disturbance observer method is relatively simple method in comparison with Luenberger observer. The proposed algorithms are successfully presented with simulations and verified by experimentally.